GeoLogix® Series Geothermal Heat Pump 3 tons, Two-Stage, Single-Phase, R410A

Capacity Modulation: Full/Part; Ground Water Heat Pump - Cooling BtuH 59°F EWT: 41,800/30,000; Ground Water Heat Pump - COP: 4.6/5.0; Ground Water Heat Pump - EER: 24.6/30.5; Ground Water Heat Pump - Heating BtuH 50°F EWT: 35,000/25,400; Hot Water Generator Option: Y; Volts: 208/230-1-60; Water Loop Heat Pump Cooling BtuH 86°F EWT: 37,900/27,200; Water Loop Heat Pump COP: 5.4/5.9; Water Loop Heat Pump EER: 16.9/18.4; Water Loop Heat Pump Heating BtuH 68°F EWT: 41,200/30,500;

Order # :
B99-443
Mfg. # :
HTS036C1D01NNN
Brand :
Comfort-Aire
Shipping Weight :
235.00
Country of Origin :
UNITED STATES
My Johnstone Supply Price:

AVAILABILITY

Store Status
Login above to see availability

Description:

  • Variable-speed ECM2 blower motor adjusts to multiple duct system applications
  • Top of industry ARI/ASHRAE/ISO 13256-I ratings for heating COP's, cooling EER's
  • Efficient operation from 20° to 120° F entering water temperatures with flow rates as low as 1.5 GPM/ton
  • Coax and air coil freeze protection for well or closed loop installation
  • Microprocessor control provides lock-out and time delay function
  • Double isolated scroll compressor with quiet operation
  • Condensate overflow protection
  • Loop pump power block with circuit breaker
  • Hot water generator (HWG) with internal pump
  • Hot water high limit HWG pump shutdown
  • CXM controls offer LED status light with memory feature
  • Swivel water connections
  • Bi-directional thermal expansion valve
  • Easy access with three removable panels for service
  • 208/230V

Capacity Modulation: Full/Part; Ground Water Heat Pump - Cooling BtuH 59°F EWT: 41,800/30,000; Ground Water Heat Pump - COP: 4.6/5.0; Ground Water Heat Pump - EER: 24.6/30.5; Ground Water Heat Pump - Heating BtuH 50°F EWT: 35,000/25,400; Hot Water Generator Option: Y; Volts: 208/230-1-60; Water Loop Heat Pump Cooling BtuH 86°F EWT: 37,900/27,200; Water Loop Heat Pump COP: 5.4/5.9; Water Loop Heat Pump EER: 16.9/18.4; Water Loop Heat Pump Heating BtuH 68°F EWT: 41,200/30,500;

Product Specifications

Capacity ModulationFull/Part
Ground Water Heat Pump - COP4.6/5.0
Ground Water Heat Pump - Cooling BtuH 59°F EWT41,800/30,000
Ground Water Heat Pump - EER24.6/30.5
Ground Water Heat Pump - Heating BtuH 50°F EWT35,000/25,400
Hot Water Generator OptionY
Volts208/230-1-60
Water Loop Heat Pump COP5.4/5.9
Water Loop Heat Pump Cooling BtuH 86°F EWT37,900/27,200
Water Loop Heat Pump EER16.9/18.4
Water Loop Heat Pump Heating BtuH 68°F EWT41,200/30,500
Shipping Weight235.00
Shipping Width30.00
Shipping Length33.00
Shipping Height25.00

Compliance & Notes

Harmonize Code8415810110

Contact your local store for additional notes and/or restrictions

Warranty Information

WARRANTY - Johnstone Supply will administer and promptly process all warranties in accordance with the manufacturer's specific warranty policies and procedures.

WHOLESALE ONLY - Identification is required of purchasers. Possession of Johnstone's catalog does not constitute an offer to sell by Johnstone or the right to purchase from us.

RETURNS - All returns are subject to a restocking charge.

Brand Name:
Comfort-Aire
See other: Comfort-Aire - Ground & Water Source
See all: Comfort-Aire Products

Mfg. #: HTS036C1D01NNN