Description:
- Air cooled condensing units All units charged with dry nitrogen Pressure control included where listed below MCA and MFS ratings below denote Minimum Circuit Ampacity and Maximum Fuse Size Last letter in mfg. # designates unit features: A or K: no receiver, with power cord B: with receiver and power cord C: with receiver, power cord, and service valves S: no receiver, with service valves and power cord
B/M: 32G326-59; BtuH Capacity @ 0°F Evap.: 2,200; BtuH Capacity @ 10°F Evap.: 2,600; BtuH Capacity @ -10°F Evap.: 1,800; BtuH Capacity @ -20°F Evap.: 1,380; BtuH Capacity @ -30°F Evap.: 980; BtuH Capacity @ -40°F Evap.: 550; Compressor #: AEA2415AAB; Height: 9.0"; HP: 1/3; Length: 19.4"; Liquid Conn.: 1/4" SAE; Max. Fuse Size: 15; Mfg. #: AEA2415AABSC; Min. Circuit Amps: 8.0; Receiver Capacity Lbs.: 2.4; Suction Conn.: 3/8" SAE; Volts: 115; Width: 13.2"; Wt. Lbs.: 52;